Exhaust Flow Requirements  
The following is based on the 2009 International Mechanical Code (IMC):  
The flow of air required for a vent hood is based on the linear length of the face  
of the hood, measured along the front side, parallel with the front of the appliance  
(refer to LENGTH in Fig. 12). The minimum net air flow for Type II hoods used with  
dishwashers is 100 CFM per linear foot of hood length. Simply multiply the hood's  
length, in feet, times 100 CFM to obtain the required flow rate.  
Subtract make-up air flow supplied directly to a hood cavity, from the total exhaust  
flow rate of the hood, if applicable.  
For hood designs not covered by these calculations consult the latest edition of the  
IMC or other local codes.  
LENGTH  
CLEARANCE  
HEIGHT  
Fig. 12  
ELECTRICAL CONNECTIONS — DISHWASHER  
Electrical and grounding connections must comply with the  
applicable portions of the National Electrical Code, ANSI/NFPA 70, latest  
edition, and/or other local electrical codes.  
Disconnect the electrical power to the machine and follow  
lockout/tagout procedures. There may be multiple circuits. Be sure all  
circuits are disconnected.  
Connect a permanent electrical power supply to the terminal block in the control  
box on top of the machine. Refer to the machine data plate for proper connection  
information and the electrical diagram located inside the control box cover.  
– 14 –  
GeneralDetails
NameHOBART CLCS66e ML Series Dishwasher
MakeHOBART
LanguageEnglish
FiletypePDF (Download)
File size2.18 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
HOBART AM16 Commercial Dishwasher
HOBART AM16 Commercial Dishwasher
HOBART S.48820 Commercial Dishwasher
HOBART S.48820 Commercial Dishwasher

HOBART CLCS66e ML Series Dishwasher