Exhaust Flow Requirements
The following is based on the 2009 International Mechanical Code (IMC):
The flow of air required for a vent hood is based on the linear length of the face
of the hood, measured along the front side, parallel with the front of the appliance
(refer to LENGTH in Fig. 12). The minimum net air flow for Type II hoods used with
dishwashers is 100 CFM per linear foot of hood length. Simply multiply the hood's
length, in feet, times 100 CFM to obtain the required flow rate.
Subtract make-up air flow supplied directly to a hood cavity, from the total exhaust
flow rate of the hood, if applicable.
For hood designs not covered by these calculations consult the latest edition of the
IMC or other local codes.
LENGTH
CLEARANCE
HEIGHT
Fig. 12
ELECTRICAL CONNECTIONS — DISHWASHER
Electrical and grounding connections must comply with the
applicable portions of the National Electrical Code, ANSI/NFPA 70, latest
edition, and/or other local electrical codes.
Disconnect the electrical power to the machine and follow
lockout/tagout procedures. There may be multiple circuits. Be sure all
circuits are disconnected.
Connect a permanent electrical power supply to the terminal block in the control
box on top of the machine. Refer to the machine data plate for proper connection
information and the electrical diagram located inside the control box cover.