HOBART CLCS66e ML Series Dishwasher
GAS SPECIFICATIONS
Flowing Gas Pressure - Not Static
Inches W.C. (Water Column)
Type of
Connection
Models
BTU/Hr
Gas
Line Size
Incoming Line Pressure
Manifold
Pressure
Minimum
Maximum
CL44e, CLPS66e, CLCS66e
CL54e, CLPS76e, CLCS76e
CL44eR, CLPS66eR, CLCS66eR
CL54eR, CLPS76eR, CLCS76eR
Natural
Propane 78,000
78,000
1/2" NPT
1/2" NPT
3.5" W.C.
9.0" W.C.
7.0" W.C.
11.0" W.C.
3.2" W.C.
8.2" W.C.
CL64e, CLPS86e, CLCS86e
CL64eR, CLPS86eR, CLCS86eR Propane 156,000
Natural 156,000
3/4" NPT
3/4" NPT
3.5" W.C.
9.0" W.C.
7.0" W.C.
11.0" W.C.
3.2" W.C.
8.2" W.C.
Dissipate test pressure from the gas supply line before reconnecting the appliance
and its manual shutoff valve to the gas supply line.
Failure to follow this procedure may damage the gas valve.
Gas heat machines must be provided with a means to exhaust
the flue gases to the exterior of the building.
Refer to Venting Requirements on pages 10 – 14.
The dishwasher must be installed so that the flow of combustion and ventilation
air will not be obstructed. Ensure that no electrical cables or plumbing are routed
over the gas flue area. Adequate clearances for air openings into the combustion
chamber must be provided. Make sure there is an adequate supply of make-up air
in the room to allow for combustion of the gas at the burner(s).
Keep the appliance area free and clear from all combustible substances. Do not
obstruct the flow of combustion and ventilation air. The dishwasher must have a
minimum clearance from combustible construction of 3" at the rear and 0" at the
sides. A clearance of 23" must be provided at the front and 20" at each end of the
dishwasher for servicing and proper operation.
The burner is ignited automatically by solid-state electronic circuitry. There is no
pilot light. Gas flow is regulated by the temperature control circuit.
VENTING REQUIREMENTS
CLeR units will require a back draft damper in the ventilation system.
(To be supplied and installed by others).
Type II Canopy Hood
Most commercial dishwashers must be provided with external venting per local
codes. Theexceptioniselectricorsteamheatmachinesoperatinginthechemicalor
lowtemperaturesanitizingmodewheretheexistingroomventilationwillcompensate
for the vapors produced. The local authority has final jurisdiction over this matter.
Venting can be provided by either a canopy hood over the whole machine (Fig. 9)
or by the pant-leg duct connection (Fig. 10).
– 10 –